AFC fans are used in ventilation installations, where the fan is connected to air ducts at the inlet and outlet. The compact and solid construction of AFC fans and availability of a variety of special designs allows for their broad application in various ventilation systems.
Contact us

Application

AFC fans are used in ventilation installations, where the fan is connected to air ducts at the inlet and outlet. 

The compact and solid construction of AFC fans and availability of a variety of special designs allows for their broad application in various
ventilation systems, including:

  • General ventilation systems of commercial and industrial premises
  • Ventilation of storage facilities
  • Ventilation of garages, public utility buildings, etc.

Construction

  • rotor is made of glass-fibre reinforced polypropylene, dynamically balanced according to ISO 1940-1,
  • welded steel sheet housing,
  • bolted steel motor plate,
  • flow direction impeller -> motor,
  • fan painted black RAL 9005,
  • inspection cover on the housing,
  • installation in a horizontal or vertical position,
  • fans for operation at temperatures from -20⁰C to 60⁰C - single-phase models,
  • fans for operation at temperatures from -20⁰C to 40⁰C - three-phase models.

Electric motor

  • EC motors (BLDC) single-phase 230V 50Hz and three-phase 400V 50Hz,
  • degree of protection IP 55,
  • single-phase motors with the possibility of regulation by analog voltage 2-10V or current 4-20mA,
  • three-phase motors with the possibility of regulation by analog voltage 2-10V or current 4-20mA signal, or control by modbus RTU.

On request

  • aluminum impeller,
  • painting in a color other than the standard,
  • painting in a higher corrosivity category,
  • galvanized steel sheet housing,
  • housing made of stainless steel 1.4301,
  • housing made of acid-proof steel 1.4404,
  • motor for other than standard voltage and power frequency,
  • motor with a different degree of protection,
  • motor with a different insulation class,
  • motr equipped with sensors or additional cooling.

Technical assistance

Choose a fan www.fanselectoronline.com

m3/h
Pa

Work characteristics

Dimensions

Type C N ØA ØB ØD ØE
  mm mm mm mm mm mm
AFC/EC-402-075S 390 8 480 450 400 12
AFC/EC-402-110S 390 8 480 450 400 12
AFC/EC-452-110S 430 8 530 500 450 12
AFC/EC-402-075T 390 8 480 450 400 12
AFC/EC-402-110T 390 8 480 450 400 12
AFC/EC-402-150T 390 8 480 450 400 12
AFC/EC-402-220T 390 8 480 450 400 12
AFC/EC-402-300T 390 8 480 450 400 12
AFC/EC-452-110T 430 8 530 500 450 12
AFC/EC-452-150T 430 8 530 500 450 12
AFC/EC-452-220T 430 8 530 500 450 12
AFC/EC-452-300T 430 8 530 500 450 12
AFC/EC-452-400T 430 8 530 500 450 12
AFC/EC-502-220T 520 12 590 560 500 12
AFC/EC-502-300T 520 12 590 560 500 12
AFC/EC-502-400T 520 12 590 560 500 12
AFC/EC-562-300T 580 12 650 620 560 12
AFC/EC-562-400T 580 12 650 620 560 12
AFC/EC-632-400T 540 12 720 690 630 12
AFC/EC-564-037T 450 12 650 620 560 12
AFC/EC-564-055T 450 12 650 620 560 12
AFC/EC-564-075T 450 12 650 620 560 12
AFC/EC-564-110T 450 12 650 620 560 12
AFC/EC-564-150T 450 12 650 620 560 12
AFC/EC-634-055T 540 12 720 690 630 12
AFC/EC-634-075T 540 12 720 690 630 12
AFC/EC-634-110T 540 12 720 690 630 12
AFC/EC-634-150T 540 12 720 690 630 12
AFC/EC-634-220T 540 12 720 690 630 12
AFC/EC-714-110T 470 16 800 770 710 12
AFC/EC-714-150T 470 16 800 770 710 12
AFC/EC-714-220T 470 16 800 770 710 12
AFC/EC-714-300T 470 16 800 770 710 12
AFC/EC-714-400T 470 16 800 770 710 12
AFC/EC-804-150T 620 16 890 860 800 12
AFC/EC-804-220T 620 16 890 860 800 12
AFC/EC-804-300T 620 16 890 860 800 12
AFC/EC-804-400T 620 16 890 860 800 12
AFC/EC-904-300T 600 16 1005 970 900 15
AFC/EC-904-400T 600 16 1005 970 900 15

Additional equipment